Product Description
The in-ceiling LGH-15RVX3-E Lossnay Fresh Air Energy Recovery Ventilation system provides the ultimate in energy efficient ventilation to ensure your home or office has a constant supply of healthy, fresh air. Air volume: 42l/s. (WxDxH, mm) 780 x 610 x 289. Weight: 20kg. Operated by the simple to use PZ-62DR† wall mounted backlit LCD controller.
- Description
- Additional information
- Specifcations
- Downloads
- Support
Description
Optimise Indoor Air Quality and Maximise Efficiencies with Lossnay Fresh Air Energy Recovery Ventilation
As an energy reclaim mechanical ventilation system, Lossnay LGH-RVX3-E models are equipped with chemically treated paper core to recover sensible and latent heat from the outgoing stale air to pre-warm (or pre-cool) incoming fresh air.
The LGH-RVX3-E range allows buildings to maximise efficiencies whilst maintaining healthy CO2Â and humidity levels for better indoor air quality.

After launching its first generation in 1970, Lossnay has evolved by always looking ahead of the air conditioning needs of the times, which continue to diversify. The technology is used in a wide range of applications and units have been widely adopted in residences, office buildings, hospitals, schools, etc.

Make Heat Recovery Ventilation Visible – with Advanced Lossnay Wi-Fi Control
Elevating air quality and maximising energy efficiencies has never been easier, because now the power is in your hands.
- See by how many degrees† Lossnay is pre-warming or cooling your home in real time, helping you save on your power bill because less additional heating is required to get a room up to temperature.
- And in summer, monitor by how many degrees Lossnay reduces the average temperature in your home, using Automatic Free Cooling^Â Mode.
- The app will also proactively remind you when it is time to clean your filters to maximise both cost efficient operation and health benefits.
Lossnay Wi-Fi Control truly is the smart evolution in fresh air ventilation.
*The following compatible Lossnay models can be connected to the Wi-Fi Control Service via a compatible Wi-Fi Interface MAC-588IF-E: VL-250/350/500 Vertical, LGH-RVX-E-1 and LGH-RVS-E Series only.
†The outside ‘Fresh Air’ and the inside ‘Avg Temp’ air temperatures are measured by the built-in sensors that are centrally located in the main Lossnay Ventilation unit.
^In comparison to using a dedicated cooling device. The unit will continue to use a small amount of power to bring colder fresh air from outside.

The Need for Fresh Air
Poor air quality can be attributed to many problems arising in the workplace and in the home. It is believed to contribute to a significant loss in productivity, low morale and higher rates of sickness. Providing good ventilation in residential and commercial buildings enables occupants to live and work comfortably and safely.
Total Heat Exchange Ventilation Maximises Heating or Cooling Efficiencies
The key to Lossnay is the unique heat transfer core. Through the Lossnay Core, up to 88%*Â of the energy in the stale exhaust air is recovered and transferred to pre-warm (or cool) incoming fresh, filtered air.
For example, in winter a building that has an inside temperature of 20°C and 4°C air outside, the incoming fresh air can be warmed to over 18°C by transferring through a Lossnay Ventilation System and benefitting from the efficient energy transfer process. The building’s air conditioning systems no longer have to work as hard to maintain desired indoor air temperatures.

Improved Airflow Range
Variable air control
The default fan speed value (Fan speed 1: 25%, Fan speed 2: 50%, Fan speed 3: 75%, and Fan speed 4: 100%) of both supply air and exhaust air can be adjusted flexibly. Within the range between 25% and 100%, airflow can be adjusted by 5% increments to satisfactorily meet the designed airflow rate.
Low Noise Design
By providing a range of air volume for each fan speed, sound levels can be reduced to achieve low noise.
Improved External Static Pressure
External static pressure has been improved compared to previous models. By increasing the external static pressure, highly flexible duct work becomes possible thus renewal from existing equipment is easy.
Weekly Timer
Optimise airflow for each application with the new remote controller, PZ-62DR-E†. The operation pattern for each day of the week, ON / OFF and air volume can be set using the weekly timer function (up to eight separate Start/Stop patterns per day over a 7 day period). Compared to previous models, much finer operation control contributes to enhanced energy saving operation. With a wider range of air volumes the Lossnay RVX units enable optimised ventilation not just at different times of the day, but for different days of the week as well, enabling further energy savings.

Optimised Control with Optional CO2Â Sensor
Optimise airflow for each application with the new remote controller, PZ-62DR-E.
A Mitsubishi Electric CO2Â sensor connected directly to the LGH-RVX3-E unit optimises the fan speed according to the levels CO2Â detected, ensuring indoor air quality is maximised and total heat exchange efficiency is improved. There are two sensor options available, a wall mounted type or built-in.



-
Two types of CO2Â sensors are available: wall-mounted and duct-mounted types.
Power is supplied to the CO2Â sensor from the Lossnay board.
Fan speed automatically changes from 25% to 100% (16 steps) depending on the level of CO2Â concentration.

- Both upper and lower limits can be adjusted.
Upper limit: from 600 to 2000 ppm.
Lower limit: from 300 to (upper limit – 300) ppm. 50 ppm increments.
Optional CO2Â Monitoring
With the option of an additional CO2Â sensor. When connected with the optional Wi-Fi Control Interface, CO2Â levels can be viewed in real-time making it ideal for schools, medical facilities and offices.
It is well known that poor air quality impacts health, wellbeing and concentration levels. In conjunction with the CO2Â sensor, the Lossnay LGH-RVX3-E system intuitively adjust airflow to ensure optimum air quality, no matter how many people are in the room.
Dual Barrier Coating
Dual Barrier Coating prevents dust and oil build-up on the interior of the Lossnay unit, helping to keep it clean for optimal performance. A water-repellent effect is achieved by creating a coating film that has nano-sized concave-convex structures formed by silica nanoparticles made of water-repellent fluororesin and micron-sized concave-convex structures formed by combining micronsized special-shaped particles (silicate) with the silica nanoparticles. At the same time, the uneven structure forms an air layer that suppresses the adhesion of dust and sand that contain a lot of humidity, reducing the amount of dirt that adheres to the substrate.


Upgraded Filters
The standard filter has been improved from Coarse 35% to Coarse 60% (measured by ISO16890: 2016).
Upgraded Filters
The standard filter has been improved from Coarse 35% to Coarse 60% (measured by ISO16890: 2016).

Additional information
| Controller Type | Advanced Wi-Fi Control, Wireless Controller |
|---|
Technical Specifications: LGH-RVS-E Series
| Heat Exchange System | Air to Air Total Heat Exchange (Sensible + Latent) |
| Core Material | Partition spacing plate – treated paper |
| Dimensions (WxDxH) | 780mm x 610mm x 289mm |
| Unit Weight | 20.0 kg |
| Duct Size | 100 mm (Insulated) |
| Operating Range | –15°C to +40°C (OA Temp), 80% RH or less |
| Power Supply | 230V ± 10% / Single Phase / 50 Hz |
Performance (Heat Recovery Mode)
| Fan Speed | Air Volume | Input Power | Heating Efficiency | Noise Level |
|---|---|---|---|---|
| Speed 1 | 10 L/s | 10.0 W | 81.5 % | 17 dBA |
| Speed 2 | 21 L/s | 15.0 W | 78.0 % | 18 dBA |
| Speed 3 | 31 L/s | 30.0 W | 75.5 % | 22 dBA |
| Speed 4 | 42 L/s | 55.0 W | 73.5 % | 27 dBA |
Notes:
* Static pressure maximum includes Return Air Fan. OA = Outside Air, RH = Return Humidity.
** Dehumidification based on OA 0°C/80% RH and IA 20°C/60% RH at Speed 4.
*** Noise dBA measured at 1.5m under panel.
**** Complies with Standards: AS/NZS 60335.2.80 and AS/NZS CISPR14.1
LGH-15RVX3-E
Lossnay LGH-RVX3 Energy Recovery Ventilation (6,099 KB)
How to clean your filters and core (1,386 KB)
Installation Manual (4,379 KB)
Warrenty
5 year parts and labour warranty. For full details view warranty terms and conditions.pdf (199 KB)
Related Products
Mitsubishi Electric Lossnay VL100-W wall-mounted ventilation system
The wall-mounted VL100 Lossnay Fresh Air Energy Recovery Single Room Ventilation unit provides energy efficient ventilation to ensure individual rooms have a constant supply of healthy, fresh air. And because the unit is ductless in design, it means the system is ideal for homes and buildings where there is no roof space to install a heat exchanger.
Mitsubishi VL100-D Single Room Fresh Air Ducted Ventilation with Lossnay Energy Recovery
The Ducted VL100ZSKRT-E Lossnay Fresh Air Energy Recovery Single Room Ventilation unit provides energy efficient ventilation to ensure individual rooms have a constant supply of healthy, fresh air. And because the unit is ducted in design, it means the system can be installed in the roof or attic space, so it is unobtrusive and hidden away. Wireless Remote Controller included.
Mitsubishi VL220 Balanced Pressure Heat Recovery Ventilation
Mitsubishi VL250 Home Fresh Air Heat Recovery Ventilation
The slimline, Vertical VL250 Lossnay Fresh Air Heat Recovery Ventilation System provides the ultimate in energy efficient ventilation to ensure your home has a constant supply of healthy, fresh air. With its small upright footprint, it can be placed in the garage or a utility cupboard and is not limited to an in-roof installation. Outside air and return air ducts are located on the right side. Equipped with a Wi-Fi adapter for easy operation and real-time heat recovery monitoring and filter clean reminders*
Mitsubishi VL500 Home Fresh Air Heat Recovery Ventilation
The slimline, Vertical VL500 Lossnay Fresh Air Heat Recovery Ventilation System provides the ultimate in energy efficient ventilation to ensure your home has a constant supply of healthy, fresh air. With its small upright footprint, it can be placed in the garage or a utility cupboard and is not limited to an in-roof installation. Outside air and return air ducts are located on the right side. Equipped with a Wi-Fi adapter for easy operation and real-time heat recovery monitoring and filter clean reminders*